J-YY

Application Area
Cable Construction
Inner Conductor
Electrolytic Copper Wire
EN, IEC 60228
Insulation
PVC, DIN VDE 0815 Suitable for isolated color
70°C, EN 50290-2-21 TM52
Stranding
Twisted in group
Outer sheath
PVC, RAL 3000 Red,
EN 50290-2-22 TM52
Technicial Properties
Operating Temperature -30°C … + 70°C
Min. Bending Radius 10 x D
Operating Voltage 300 V
Insulation Resistance 100 MΩ km
Max. Capacitance 100 nF/km
Max. Capacitance Unbalance 300 pF / 500m
Test Voltage  
< 1.00 mm 800V
≥ 1.00 mm 1000V
Packing 500 / 1000 m

Standards
TSE K 173
Euro Class
Eca
Flame Retardancy Test
EN 60332-1-2
Conductor Cross Section
(mm) - (mm²)
Conductor Resistance max.
(Ohm/km @ 20 °C)
  0.60 mm 130 Ω/km
    0.80 mm   73.20 Ω/km
    1.00 mm   44.40 Ω/km
    1.00 mm²  36.20 Ω/km
  1.50 mm² 24.20 Ω/km
  2.50 mm² 14.80 Ω/km

 

No. Of Cores x Cross Section
(mm) - (mm²)
Overall Diameter
(mm)
Copper Weight
(kg/km)
Cable Weight
(kg/km)
1 x 2 x 0.60 4.9 7.0 27
2 x 2 x 0.60 5.3 13.0 47
3 x 2 x 0.60 6.1 18.0 50
4 x 2 x 0.60 6.6 23.0 58
5 x 2 x 0.60 7.3 32.0 81
6 x 2 x 0.60 7.8 46.0 92
10 x 2 x 0.60 8.8 56.0 110
       
1 x 2 x 0.80 5.9 13.0 38
2 x 2 x 0.80 6.8 22.0 58
3 x 2 x 0.80 5.3 32.0 78
4 x 2 x 0.80 8.8 42.0 98
5 x 2 x 0.80 10.3 62.0 138
6 x 2 x 0.80 11.0 82.0 168
10 x 2 x 0.80 12.8 102.0 218
       
1 x 2 x 1.00 6.8 16.0 42
2 x 2 x 1.00 8.4 30.0 60
3 x 2 x 1.00 10.0 45.0 118
4 x 2 x 1.00 11.2 62.0 192
6 x 2 x 1.00 13.0 90.0 192
8 x 2 x 1.00 14.6 120.0 246
10 x 2 x 1.00 16.0 148.0 303
       
1 x 2 x 1.50 7.8 30.0 62
2 x 2 x 1.50 9.2 55.0 110
3 x 2 x 1.50 12.0 80.0 167
4 x 2 x 1.50 13.4 108 207
6 x 2 x 1.50 16.0 160.0 302
8 x 2 x 1.50 18.2 212.0 398
10 x 2 x 1.50 19.5 264.0 476